DUAL OUTPUT MODULAR TELECOM POWER SUPPLY
SPECIFICATIONS for MODEL RP500
DESCRIPTION: A 19"w x 5.25"h rack mount chassis containing up to four separate modules, each rated for 2.2A(DC) and 0.2A(AC) output current. The modules operate in a parallel mode. The fourth module can provide output power or N+1 redundancy.
INPUT POWER: 90-132/180-264 VAC, Jumper Selectable. (Automatic Range Selection is an option) 47-63hz
MAXIMUM DC OUTPUT: -48VDC @8.8A (4 Modules, no redundancy)
DC OUTPUT REGULATION: Less than 1%
DC OUTPUT RIPPLE: Less than 0.5% peak to peak
OUTPUT ISOLATION: -48 VDC isolated from chassis ground. AC output is referenced to -48VDC output.
MAXIMUM AC OUTPUT: 93VAC @0.8A (4 modules, no redundancy) with 100% duty cycle. (for 35% duty cycle this would increase to 1.0A)
AC OUTPUT FREQUENCY: 20Hz +/- 10% is standard. (17,20,25, and 50Hz +/- 10% Switch Selectable is an option)
AC OUTPUT REGULATION: Less than 10% for the full input voltage range and no load to full load.
AC OUTPUT WAVE FORM: Simulated sine wave with less than 20% distortion.
CURRENT LIMITING: All outputs have current limiting with full protection and auto recovery.
OUTPUT INDICATOR: Green LED on the module indicates that all outputs are operating. (External signal to indicate an alarm condition is an option.)
MODULE FAILURE PROTECTION:A failure in any module will result in its outputs being automatically taken off line.
TEMPERATURE RANGE: Ambient temperature range is 0 to 50 degrees C for full load operation.
EMI DESIGN STANDARDS: Compliance with FCC 20780, Part 15, Class B and EN55022, Class B and EN50082-1.
SAFETY DESIGN STANDARDS:Compliance with EN60950, UL1950 3rd edition and CSA C22.2-950.